Commercial Grade Item Upgrade Dedication Form
SNF-6105, Rev. 0
ECN No. NIA CGI No. CGl-SNF-D-30-C1-063 Page 2 of 11
rie: Local Exhaust S stem - Fans, Fan Motors, Backdraft Dam ers, and isolation Dam ers
Section 3 Failure Effects Evaluation
A. Part/Component Safety Function:
1. Maintain routing of potentially contaminated and/or flammable air stream through the filtration system.
2. Prevention of hi h concentrations of h dro en as buildin u within the MCO's or the ductwork.
B. Part/Component Functional Mode:
Safety Function #1: X ACtive Passive Active - Mechanical or Electrical change of state is required to occur for
SaeyFnto_1_XAtv asv the component to perform its safety function
Safety Function #2: Active X Passive Passive - Change of state is not required for the component to perform
its safety function
Safety Function #3: Active Passive
C. Host Component Safety Function (if applicable): N/A
1.
D. Failure Mode(s) and the effects on component or system safety function (see Worksheet 1):
1. Fan shaft can seize or fail
2. External events that causes structural component failure
3. Seismic 3!1 Protection for adjacent SS SSCs -Containment
Section 4 Environmental & Natural Phenomena Hazard Design
Environmental Qualification Required: If yes: Environmental Qualification Requirements
Yes Limiting Environmental Conditions:
No X Environmental Condition A Cqr aty Functions:
____________ _________________Qualification Period:
Natural Phenomena Hazard (NPH) Design Required: If yes: NPH Design Requirements
Performance Category: PC-2
Yes X HNF-PRO-97, Rev. 0, W-441.C1 NPH Design Req'ts.:
_____. Required Safety Functions: Seismic 3/1 Protection for
No adjacent SS SSCs " Containment
Section 5 Component Functional Classification
SafetyCassj(SC) General Service X Safet Si nificant SS
If part/component classification is different from host component/system, document basis. N/A
Sections 6 and 7 (Reserved)
Section 8 References (for Functional Classification)
National Codes/Standards: ASHRAE, SMACNA
Safety Analysis Report (SAR): HNF- 3553, Rev. 0, Annex B
Drawings: H-1-82206, Sht. 1, Rev. 2, HNF-SD-SNF-SEL-002, Rev. 7
Vendor Manual/Manufacturer/Supplier Information: Catalog Cut Sheets " Barry Blower, Ruskin Dampers3/29/00
Upcoming Pages
Here’s what’s next.
Search Inside
This report can be searched. Note: Results may vary based on the legibility of text within the document.
Tools / Downloads
Get a copy of this page or view the extracted text.
Citing and Sharing
Basic information for referencing this web page. We also provide extended guidance on usage rights, references, copying or embedding.
Reference the current page of this Report.
Van Katwijk, Carl. Local Exhaust System Fans and Fan Motors and Backdraft Dampers and Isolation Dampers, report, March 30, 2000; United States. (https://digital.library.unt.edu/ark:/67531/metadc742278/m1/8/: accessed May 11, 2024), University of North Texas Libraries, UNT Digital Library, https://digital.library.unt.edu; crediting UNT Libraries Government Documents Department.