PUREX EXH SYSTEM ACCEPTANCE TEST PROCEDURE
6.3.13 Connect the Hall Effect limit switch test box as follows for testing limit switches
on the EFl-3 inlet damper IA actuator:
" Terminals ZOS-CD-32-1A, TB-1 to TS5-EF1-3-4 for the left-hand
(RPl) extended limit switch.
- Terminals ZCS-CD-32-1A, TB-3 to TS5-EF1-3-8 for the left-hand
(RP1) retracted limit switch.
- Terminals ZOR-CD-32-1A, TB-6 to TS5-EF1-3-12 for the right-hand
(RP2) extended limit switch.
" Terminals ZCR-CD-32-IA, TB-8 to TS5-EF1-3-16 for the right-hand
(RP2) retracted limit switch.
6.3.14 Connect the 24 Vdc test power supply to T8-9 (+)24 Vdc and (-) DC Common
on the Hall Effect limit switch test box.
6.3.15 Energize the 24 Vdc test power supply.
NOTES
When a limit switch is actuated, a red light will be illuminated on the Hall Effect test box.
When a left-hand (RPI) type limit switch is actuated, the red light on the switch will be
illuminated.
When a right-hand (RP2) type limit switch is actuated, the green light on the limit switch will not
be illuminated.
6.3.16 Place a magnet near the left-hand retracted limit switch and verify the following:
- The red light on the Hall Effect test box is illuminated.
- The red light on the limit switch is illuminated.
6.3.17 Remove the magnet and verify that both red lights are no longer illuminated.
6.3.18 Place a magnet near the right-hand retracted limit switch and.verify the
following:
- The red light on the Hall Effect test box is illuminated.
- The green light on the limit switch is not illuminated.
DOCUMENTS., REVISIONNO.: PAGENO.:
HNF-SD-CP-ATR-087 0 46 OF 67
Upcoming Pages
Here’s what’s next.
Search Inside
This report can be searched. Note: Results may vary based on the legibility of text within the document.
Tools / Downloads
Get a copy of this page or view the extracted text.
Citing and Sharing
Basic information for referencing this web page. We also provide extended guidance on usage rights, references, copying or embedding.
Reference the current page of this Report.
Blackaby, W.B. PUREX exhaust ventilation system installation test report, report, October 7, 1997; Richland, Washington. (https://digital.library.unt.edu/ark:/67531/metadc687113/m1/48/: accessed April 26, 2024), University of North Texas Libraries, UNT Digital Library, https://digital.library.unt.edu; crediting UNT Libraries Government Documents Department.