DS-76327 RD Rev 2
ULL3 Page 9
reactivity for reactor operation.
E Coolant Requirements with Irradiated Fuel in the Reactor
1. During shutdown conditions the minimum flow shall be 1000 GPM at the
B, C, D, DR, F, and H Reactors and 2000 GPM to the K Reactors, and there
shall be a positive pressure differential on the top fuel tubes.
2. Coolant water shall be available from reservoirs during reactor operation
to provide the following coolant capacities:
Available Water Storage - 106 cal.
B,DDR,F,H C KE,KW
Full normal flow for 15 minutes 1.40 1.58 3.15
Transient shutdown plus minimum 6.35 7.17 13.10
of 24-hour shutdown cooling
TOTAL 7.75 8.75 16.25
3. Each reactor coolant system shall consist of three independent, reliable
sources of coolant supply as follows:
a. Primary Cooling System
The primary cooling system shall be designed to:
1) Be capable of providing adequate process channel cooling during
all phases of normal reactor operation and shutdown.
b. Secondary Cooling System
The secondary cooling system shall be designed to:
1) Be capable of providing adequate process channel cooling indefinitely
immediately following a reactor scram from full level, assuming
instantaneous loss of power to the primary cooling system. The
minimum design flow of this system shall be as follows:
EJLASSFI--
Upcoming Pages
Here’s what’s next.
Search Inside
This report can be searched. Note: Results may vary based on the legibility of text within the document.
Tools / Downloads
Get a copy of this page or view the extracted text.
Citing and Sharing
Basic information for referencing this web page. We also provide extended guidance on usage rights, references, copying or embedding.
Reference the current page of this Report.
Owsley, G. F. Operating limits Hanford Production Reactors. Revision 2, report, May 20, 1963; Richland, Washington. (https://digital.library.unt.edu/ark:/67531/metadc1277579/m1/13/: accessed July 16, 2024), University of North Texas Libraries, UNT Digital Library, https://digital.library.unt.edu; crediting UNT Libraries Government Documents Department.