100-C water plant
Description:
System curves for each portion of the C Area Water Plant were obtained from referenced work and are presented in figures. Field test data, corroborating the calculated curves, are presented as singular points on the same graphs. Present maxima capacity of the C Area Filter Plant was 121,000 gpm with 118,000 gpm available for use as primary reactor coolant. Modifications to the filter effluent piping would increase this available flow to about 180,000 gpm. Of the 118,000 gpm available for C Reac…
more
Date:
February 20, 1961
Creator:
Agar, J. D.
Partner: