Sodium-fire control by space isolation with nitrogen flooding: FFTF proof test F2
Description:
Sodium fire protection by space isolation with nitrogen flooding was evaluated by performing a large-scale sodium fire test within a mockup of an FFTF secondary sodium system pipeway. The full scale (3350 ft/sup 3/) mockup was initially filled with air and its leak tightness set to correspond to that expected in an actual FFTF pipeway. The basis for specifying the rate of nitrogen flood gas is discussed ad the experimental verification provided. Nitrogen flooding was activated 15 minutes after …
more
Date:
June 1, 1974
Creator:
Hilliard, R.K. & Muhlestein, L.D.
Item Type:
Refine your search to only
Report