Exhaust Fan Temperature Switch

PDF Version Also Available for Download.

Description

The 13000 cfm 'emergency' vent fan must be protected from over cooling which would result in a mechanical failure. Over cooling could result from a catastrophic cryogen release from the cryostat(s) or Argon Storage Dewar. In order to protect the fan, a VPT has been calibrated for -31 C to open a switch which sends a signal to allow warm gas to enter the sump by means of a motor controlled louver installed at 'sidewalk level' in the ductwork between the assembly hall and the Argon Dewar Enclosure. The bulb of the VPT is enclosed in a thermal well and ... continued below

Physical Description

5 pages

Creation Information

Ball, G. S. May 11, 1989.

Context

This report is part of the collection entitled: Office of Scientific & Technical Information Technical Reports and was provided by UNT Libraries Government Documents Department to Digital Library, a digital repository hosted by the UNT Libraries. It has been viewed 46 times . More information about this report can be viewed below.

Who

People and organizations associated with either the creation of this report or its content.

Author

Publisher

Provided By

UNT Libraries Government Documents Department

Serving as both a federal and a state depository library, the UNT Libraries Government Documents Department maintains millions of items in a variety of formats. The department is a member of the FDLP Content Partnerships Program and an Affiliated Archive of the National Archives.

Contact Us

What

Descriptive information to help identify this report. Follow the links below to find similar items on the Digital Library.

Description

The 13000 cfm 'emergency' vent fan must be protected from over cooling which would result in a mechanical failure. Over cooling could result from a catastrophic cryogen release from the cryostat(s) or Argon Storage Dewar. In order to protect the fan, a VPT has been calibrated for -31 C to open a switch which sends a signal to allow warm gas to enter the sump by means of a motor controlled louver installed at 'sidewalk level' in the ductwork between the assembly hall and the Argon Dewar Enclosure. The bulb of the VPT is enclosed in a thermal well and will be placed in the gas stream directly above the fan. The switching unit will be mounted nearby on the wall in order to isolate it from vibrational effects. Should the fan be activated due to a cryogen release, it should not experience any problems when operating above -40 C. The switch was set and checked in a saturated calcium chloride solution cooled to -31 C by running cold gaseous Nitrogen through a copper tube coiled in a dewar. Switching temperature was measured by a thermocouple tied to the VPT bulb. The thermocouple was checked in LN2, in an ice water bath, and against an ordinary thermometer (which was assumed to be accurate to plus or minus 0.3 C) at room temperature. The results are shown below in 'Table 1' By interpolation of the data, thermocouple error at -31.0 C was found to be 0.43 C on the warm side. Since this error was small, it was ignored. 'Table 2' shows the results of the tests. Ten readings were taken with the switch wired in the 'normally open' mode. This results in a signal at room temperature. The worst deviation was 2.5 C. Three readings were then taken from the 'normally closed' wiring arrangement (the way it will be wired for installation). The greatest deviation was 1.2 C. The next day, the switch was checked five times wired in the 'normally open' configuration. The greatest error was 1.1 C. A graph has been prepared showing the switching and resetting temperatures. The errors these tests bore out do not threaten the exhaust fan and are therefore acceptable.

Physical Description

5 pages

Language

Item Type

Identifier

Unique identifying numbers for this report in the Digital Library or other systems.

  • Report No.: FERMILAB-D0-EN-210
  • Grant Number: AC02-07CH11359
  • DOI: 10.2172/1031143 | External Link
  • Office of Scientific & Technical Information Report Number: 1031143
  • Archival Resource Key: ark:/67531/metadc830054

Collections

This report is part of the following collection of related materials.

Office of Scientific & Technical Information Technical Reports

Reports, articles and other documents harvested from the Office of Scientific and Technical Information.

Office of Scientific and Technical Information (OSTI) is the Department of Energy (DOE) office that collects, preserves, and disseminates DOE-sponsored research and development (R&D) results that are the outcomes of R&D projects or other funded activities at DOE labs and facilities nationwide and grantees at universities and other institutions.

What responsibilities do I have when using this report?

When

Dates and time periods associated with this report.

Creation Date

  • May 11, 1989

Added to The UNT Digital Library

  • May 19, 2016, 3:16 p.m.

Description Last Updated

  • Aug. 30, 2016, 4:20 p.m.

Usage Statistics

When was this report last used?

Yesterday: 0
Past 30 days: 2
Total Uses: 46

Interact With This Report

Here are some suggestions for what to do next.

Start Reading

PDF Version Also Available for Download.

International Image Interoperability Framework

IIF Logo

We support the IIIF Presentation API

Ball, G. S. Exhaust Fan Temperature Switch, report, May 11, 1989; Batavia, Illinois. (digital.library.unt.edu/ark:/67531/metadc830054/: accessed October 22, 2018), University of North Texas Libraries, Digital Library, digital.library.unt.edu; crediting UNT Libraries Government Documents Department.