The purpose of this test was to determine the performance of the Reactor Plant Container Air Cooling System with four reactor coolant loops at operating temperature. Due to the fact that the test was performed with the chamber door open, no significant conclusion can be arrived at concerning the efficiency of the Air Cool System. The 1B supply fan circulated approximately 20 per cent less air than the 1A fan during the test. Later investigation revealed that the turning vanes above the 1B damper had broken loose and fallen down on top of the damper. It is not know if …
continued below
We've identified this
report
as a primary source within our collections. Researchers, educators, and students may find this report useful in their work.
Provided By
UNT Libraries Government Documents Department
Serving as both a federal and a state depository library, the UNT Libraries Government Documents Department maintains millions of items in a variety of formats. The department is a member of the FDLP Content Partnerships Program and an Affiliated Archive of the National Archives.
Added Title:
Atomic Energy Commission Report AECU-4103
Description
The purpose of this test was to determine the performance of the Reactor Plant Container Air Cooling System with four reactor coolant loops at operating temperature. Due to the fact that the test was performed with the chamber door open, no significant conclusion can be arrived at concerning the efficiency of the Air Cool System. The 1B supply fan circulated approximately 20 per cent less air than the 1A fan during the test. Later investigation revealed that the turning vanes above the 1B damper had broken loose and fallen down on top of the damper. It is not know if this situation existed during the test; however, it seems reasonable to assume that the 1B damper was possibly jammed and not fully open during the test. This test should be rerun after the deficiency is corrected and with the exhaust fan input dampers manually positioned to the open position. One of the exhaust fan inlet dampers is normally on automatic and the other on manual.
Physical Description
7 pages : tables
Notes
Digitized from microopaque cards (1).
First Issue, February 10, 1959. Second Issue, March 25, 1959.
This report is part of the following collections of related materials.
TRAIL Microcard Collection
Imaged from microcard, these technical reports describe research performed for U.S. government agencies from the 1930s to the 1960s. The reports were provided by the Technical Report Archive and Image Library (TRAIL).
The Technical Report Archive & Image Library (TRAIL) identifies, acquires, catalogs, digitizes and provides unrestricted access to U.S. government agency technical reports. The mission of TRAIL is to ensure preservation, discoverability, and persistent open access to government technical publications regardless of form or format.
Duquesne Light Company.Reactor Plant Container Air Cooling System. Section III. Second Performance.,
report,
March 25, 1959;
Washington D.C..
(https://digital.library.unt.edu/ark:/67531/metadc1240534/:
accessed November 9, 2026),
University of North Texas Libraries, UNT Digital Library, https://digital.library.unt.edu;
crediting UNT Libraries Government Documents Department.